ENERGYST AIR HANDLING UNITS
Energyst air handlers produce cold or warm air at a predetermined temperature. Air is transported via flexible air hoses and distributed by plenums or air ducting.
In combination with chillers or hot water systems, air handlers produce cold or warm air for events, tent structures, workshops, offices, storage buildings.
Technical information
Cooling/heating capacity1
|
Nominal airflow
(m3/hr.)
|
Power consumption2 (kW)
|
Sound level
dBA @ 7 m
|
Weight
(kg)
|
10/40 kW
|
2800
|
0.75
|
64
|
275
|
25/75 kW
|
7500
|
1.6
|
64
|
750
|
50/185 kW
|
9000
|
2.6
|
64
|
975
|
100/295 kW
|
20000
|
8.4
|
71.1
|
1150
|
200/585 kW
|
36000
|
16.5
|
73.2
|
1580
|
1. Cooling capacity at 7/12°C water temperature and 24°C air inlet, 50% relative humidity. Heating capacity at 90/70°C water temperature with 30% Glycol and 10°C air inlet, 50% relative humidity.
2. Including pump.
Details are given for guidance only. Actual equipment supplied may vary according to geographical location and availability.